Math Blocks — Add, Subtract, Multiply, Divide
Copied to clipboard ✓
Addition (+) — Monthly EB Bill
Three sections of an office floor:
Section A = 35 people
Section B = 28 people
Section C = 32 people
Total = 35 + 28 + 32 = 95 people
BMS example — total building energy:
Floor 1 meter = 450 kWh
Floor 2 meter = 380 kWh
Floor 3 meter = 520 kWh
Total = 1,350 kWh → shown on energy dashboard
Subtraction (-) — Home Water Tank Consumption
Morning tank level = 85%
Evening tank level = 42%
Consumed today = 85 - 42 = 43%
BMS example — filter differential pressure:
Pressure before filter = 250 Pa
Pressure after filter = 180 Pa
Differential = 70 Pa → if above 150 Pa → alarm: change filter
Multiplication (×) — Air Flow Calculation
Air velocity in duct = 4.5 m/s (from velocity sensor)
Duct cross-section area = 0.8 m² (fixed value)
Volume flow rate = 4.5 × 0.8 = 3.6 m³/s
BMS uses this to verify AHU is delivering correct airflow against design.
Division (÷) — Average Zone Temperature
Zone 1 = 23°C, Zone 2 = 25°C, Zone 3 = 24°C, Zone 4 = 26°C
Sum = 98°C
Average = 98 ÷ 4 = 24.5°C → Used for chiller plant optimisation
One faulty sensor does not drive the whole system wrong. Average of four sensors gives true floor temperature.
Related Topics
- What is BMS integration? — how a BMS connects with VFDs, energy meters, BACnet/Modbus devices and other building systems
- How to design a BMS system step by step — the complete BMS design methodology covering site survey, IO list, controller selection, sequence of operations
- What is a Building Management System (BMS)? — fundamentals of BMS controls and architecture for HVAC, lighting, energy and access
- What is BMS commissioning? — the disciplined commissioning process that turns a BMS install into a working building brain
- Browse all Control Loops & FBD topics — more from this section of the EnSmart BMS Library
Was this answer helpful?
✓ Thanks — your feedback was recorded.